TCS series high voltage reducing-voltage and compensating soft starter

 

 

TCS general introduction


1. Overview  


TCS series high voltage reducing-voltage and compensating soft start device is suitable for reducing-voltage soft start  for high voltage squirrel cage asynchronous  motor and asynchronously started synchronous motors less than 50MW in steel, petroleum, chemical, metallurgical and other industries. The device has simple operation and free maintenance with a soft start characteristic of small and constant starting current, large and gradual increased torque. It is not affected by the change of environment temperature and the impact on the power grid is very small without electromagnetic interference. It is the international advanced soft start product.

In order to attain product seriation and unification of the soft start devices and other electronic control equipments, for the convenience of user's installation, commissioning, maintenance, management, and for improving the performance and reliability of the whole system, combining with more than ten years of experience and achievement, the company can optimize the design according to the user's site, and provide TCS products and complete sets of electrical control equipment.


2. Type explanation 

Figure 2-1  Model description

For example, TCS3-20000/11means 3 serial voltage reduction and compensation solid soft start devices, suitable for 11kV motors within max power 20000kW


3. Working principle


TCS series device consists of voltage control device and reactive power control device, it also needs high voltage cabinets such as starting cabinet and running cabinet and other supporting switch cabinets. Voltage control device includes a transformer and a voltage control cabinet; reactive power control device includes one or two reactive power generators and one or two reactive power control cabinet.

Figure 3-1 TCS primary system diagram


4. Technical features


4.1 The grid side starting current is generally less than 1.5 times the rated current of the motor  during starting(2 series is generally less than 2 times), and the minimum can reach the rated current;

4.2 The grid voltage drop is generally not more than 10% during starting, the maximum not more than 15%;

4.3 The requirement for power grid capacity is low, the installed capacity of transformers can be significantly reduced and the primary equipment investment can also be drastically reduced;

4.4 The starting torque is relatively high thus it can meet the demands of different loads;

4.5  It can be used continuously and it has high repetitive precision;

4.6 No harmonic, very low voltage drop , very low influence to power energy quality and no additional active power loss;

4.7 Fully enclosed structure, no environmental restriction, safe and reliable, long life, maintenance free;

k1).

Then   .

4.8 By adjusting the transformer voltage ratio and reactive power current, the starting current which flows from bus bar can be limited within a certain range and the influence on the grid voltage.


5. Technical parameters

Table 5-1 Main performance parameters of TCS series soft start device 

Type

For motor powerkW

Rated voltage

kV

Starting current

times

Voltage drop of grid

Max starting time

Allowable starting times

TCS2

≤8000

66.6,

10,11

≤2.0

8%-15

60S

≤5 times per hour

TCS3

5000—40000

66.6,

10,11

≤1.5

7%-12

60S

≤5

TCS6

10000—50000

66.6,

10,11

≤1.2

5%-10

60S

≤5


Table 5-2 Technical parameters of TCS series soft start device device

Item

Performance index

Note

Using standard

Q/XDL14-2010

 

Installation location

Indoor

Transformer and var generator

can be installed outdoor

Applicable motor

high voltage squirrel cage asynchronous  motor and asynchronously started synchronous motors

 

Control power supply

AC220V,DC220V

 

Protection level

≥IP20

 

Control mode

PLC automatic control

 

Controller communication mode

RS485

 

Signal(input)specifications

Passive contact signal

Extensible

Signal(output)specifications

Passive contact signal AC220V,5A

Extensible

Operation mode

Touch screen

 

Interface language

Chinese And English

 


6. Dimensions and layout

Figure 6-1 TCS3-20000/11(10) outline drawing



Figure 6-2 TCS3-20000/11(10) installation drawing


Figure 6-3 TCS3-20000/11(10) arrangement drawing


Table 6-1 TCS series devices Outline dimension (W*D*H mm

type

transformer

Voltage

Control cabinet

Reactive power generator

Reactive power control device

TCS2-5000

2520*1170*2350

1000*1500*2300

1679*1170*1943

1000*1500*2300

TCS2-8000

2640*1250*2635

1000*1500*2300

2075*1380*2072

1000*1500*2300

TCS3-10000

2735*1350*2690

1000*1500*2300

2075*1380*2072

1000*1500*2300 

TCS3-12000

2755*1450*2750

1000*1500*2300

2075*1380*2422

1000*1500*2300 

TCS3-15000

2805*1450*2800

1000*1500*2300

2075*1380*2422

1000*1500*2300 

TCS6-10000

TCS3-18000

2830*1450*2830

1000*1500*2300

2075*1500*2422

1000*1500*2300 

TCS6-12000

TCS3-20000

2855*1650*2855

1000*1500*2300

2075*1500*2422

1000*1500*2300

TCS6-15000

TCS3-25000/10

2905*1650*2905

1000*1500*2300

2075*1500*2422

1000*1500*2300

TCS6-18000/10



Table 6-2  TCS series devices weightkg

type

transformer

Voltage

Control cabinet

Reactive power 

generator

Reactive power 

control cabinet

Total

weight

TCS2-5000

4300

950

2900

1000

9150

TCS2-8000

5030

950

4750

1050

11780

TCS3-10000

5750

1000

6000

1050

13800

TCS3-12000

6300

1025

6050

1075

14450

TCS3-15000

7000

1050

6100

1075

15225

TCS3-18000

7350

1050

6150

1100

15650

TCS3-20000

7600

1050

6200

1100

15950

TCS3-25000/10

8200

1100

6200

1200

16700


7. Service conditions


Ambient temperaturenot exceeding 50℃(24 hours average temperature not exceeding 45℃),and not below -10℃;

Relative humidity:  ≤90%;

Altitude :  1000m;

Placed in a room without voilent vibration and impact, and vertical tilt of the situation not exceeding 5°; 

no conductive dust and corrosive gas;

no fire and explosion danger.

Note: Please notify when ordering if the ambient temperature is below -10 for a long time or the altitude is over 1000m. 


8. Ordering instructions

The following information should be provided when ordering:

According to the motor power and voltage to determine the type of the soft start device

The motor rated parameters, motor torque vs speed curve and motor current vs speed curve should be provided;

The load type, the load moment of inertia and the load torque vs speed curve should be provided;

The minimum short-circuit capacity, maximum short circuit capacity, and the inherent load capacity of the power network should be provided;

The primary circuit diagram,cabinet layout diagram and electricity distribution room floor plan should be provided.

The cabinet color, wiring and other special requirements should also be provided.